NTG

  • Axial inline pump.
  • Sizes from DN150 to DN250.
  • Manufactured in cast iron EN-GJL-250 or EN-GJS-400.
  • IP67 protection.
  • Developed, produced, and tested according to the specifications established by standard EN IEC 60076-22-5.
Low Temperature (LT) Version:
  • Supports ambient temperatures down to -60ºC.
  • Approved to start with fluid down to -45ºC, and the kinematic viscosity must be less than 7200 mm2/s (COLD START).
ATEX version:
  • Available in size DN150.
APPLICATIONS
  • Power transformers with radiator cooling system.
FLANGE OPTIONS
  • Type of Flanges: DIN PN10.
  • Configuration: Raised or flat face.
ENGINE OPTIONS
  • Possibility of 4P, 6P or 8P engines.
CONSTRUCTION MATERIALS
  • Pump casting: Cast iron EN-GJL-250 or EN-GJS-400
  • Impeller: aluminum
  • Viton seals and fixing accessories in AISI 316
  • Terminal Boxes with IP56
WORKING LIMITS(50 Hz)
  • Maximum flow rate: up to 300 m³/h
  • Head: Up to 3 metros
  • Fluid temperature: -45ºC up to +115ºC
  • Installation: Horizontal or vertical

Talk with us